125 gq photovoltaic dedicated reclosing miniature circuit breaker
scope of application
Series 125 gq photovoltaic dedicated reclosing miniature circuit breaker (hereinafter referred to as circuit breaker), applied to ac 50 hz, rated voltage 230/400 v, rated current 125 a circuit, overvoltage, undervoltage, loss of pressure, overload, short circuit protection function. At present, the wide application of light distribution box. Conform to the standards: GB 10963.1, IEC60898-1.
the model and its meaning
main technical parameters
Electrical properties
The number of 2 p, 4 p
Functions of short circuit protection, overload protection, over/owed/loss of pressure protection
Shell Inm 125 a grade rated current value
Ue 230/400 v rated voltage
Rated current In 32, 40, 50, 63, 80 a, 100 a, 125 a
The instantaneous tripping type C
The rated short circuit breaking capacity Ics = Icn = 6000 a
Mechanical life 10000 times
Electrical life 4000 times
The overcurrent tripping characteristics are shown in table 1 and figure 1
table1
NO. | Rated current | Initial state | Test current | Set time | The expected results |
1 | 32,40,50,63 | 80,100 | cold | 1.13In | t≤1h |
t≤2h | Don't trip | ||||
2 | 32,40,50,63 | 80,100 | Then after test referred to in the preceding paragraph | 1.45In | t<1h |
t<2h | trip | ||||
3 | In≤32 | In>32 | cold | 2.55In | 1s<t<60s |
1s<1<120s | trip | ||||
4 | Full specifications | cold | 5In | 10In | t≤0.1s |
t<0.1s | Don't trip | trip |
Table 2
The expected results (A) | ≤6 10 16,20 25 32 40,50 63 80 100 125 |
Cross-sectional area of(mm2) | 1 1.5 2.5 4 6 10 16 25 35 50 |
Protection function
Over voltage protection value 265 v + 5 v
Over voltage protection recovery value 235 v + 5 v
Over voltage protection action delay 1 s
Under voltage protection value 175 v + 5 v
Under-voltage protection recovery value 190 v + 5 v
Under-voltage protection action delay 1 s
The working voltage 300 v
Loss of pressure protection function
Reset delay 20 s and 40 s
Power consumption 0.5 W
Normal working conditions and installation conditions
Protection grade IP20
1-35 was connection capacity
Using the environment temperature 40 ℃ -- 70 ℃
The wet and heat resistance 2 class
At an altitude of 2000 m or less
Pollution level 2
Circuit breaker corresponding copper wire cross-sectional area are shown in table 2
Where no significant shock and vibration environment
Install category Ⅲ
DIN standards guide installation way
Use the operating instructions
1 brand
2 models
3 the rated voltage
4 + rated current tripping types
5 control signal lamp
6 hands/automatic switch
7 the rated short circuit ability
8 up to the standard
9 indicating window
10 the electrical wiring diagram
4.1 working mode
When the product work in manual mode, the Settings below
When the switch switch from automatic mode to manual mode, switch power supply voltage automatic detection, such as entering a state allows switching voltage normal, allow manual switching.
When the product work in automatic mode, the Settings below
Overpressure value 265 v + 5 v, under voltage value to 175 v + 5 v.
Products through about 30 seconds after normal voltage, automatic reset switch when detecting voltage is normal. Unable to switch and a single flash when overvoltage, undervoltage when not closing and double flash.
Over voltage protection: over voltage (265 v + 5 v) and for 1 seconds after the trip, if after the trip voltage return to normal voltage (235 v + 5 v) and closing for 30 seconds.
Under-voltage protection, under voltage (175 v + 5 v) and for 1 seconds after the trip, if after the trip voltage return to normal voltage (190 v + 5 v) and closing for 30 seconds.
Loss of pressure protection: normal voltage drops to below 110 v more than 0.5 seconds, tripping directly, cannot be a manual switch.
4.2 the other
This product has good current limiting characteristics, arc very short time, high breaking capacity and protective properties, long service life, stable performance and reliable precision, at the same time has obvious sign the contact position of the state and control the signal light. Connection terminal adopts frame structure, solid and reliable.
Overall dimensions
ordering instructions
When placing order, please indicate the circuit breaker type, rated current value, tripping type, number, number.
Such as:
Need to order 125 gq photovoltaic dedicated small under-voltage reclosing circuit breaker, rated current is 63 a, tripping type is C, 2, 1000.
Expressed as: 125 gq 2 p C63 1000 units.